H07V-K

P/F · H07V-K · JUS N.C3.202

Low-voltage flexible PVC-insulated copper conductor (H07V-K · JUS P/F), class-5 stranded, 450/750 V.

Download datasheet (PDF)
Low-voltage flexible PVC-insulated copper conductor (H07V-K · JUS P/F), class-5 stranded, 450/750 V.

Variants

SECTION (mm²)0,75RESISTANCE (Ω/km)26,0CURRENT (air) (A)6INSUL. THK. (mm)0,6OUTER Ø (mm)2,3METAL WT. (kg/km)7,2CABLE WT. (kg/km)12,1Availability
On request
SECTION (mm²)1RESISTANCE (Ω/km)19,5CURRENT (air) (A)10INSUL. THK. (mm)0,6OUTER Ø (mm)2,4METAL WT. (kg/km)9,6CABLE WT. (kg/km)14,8Availability
On request
SECTION (mm²)1,5RESISTANCE (Ω/km)13,3CURRENT (air) (A)17,5INSUL. THK. (mm)0,7OUTER Ø (mm)3,0METAL WT. (kg/km)14,4CABLE WT. (kg/km)21,5Availability
On request
SECTION (mm²)2,5RESISTANCE (Ω/km)7,98CURRENT (air) (A)24INSUL. THK. (mm)0,8OUTER Ø (mm)3,6METAL WT. (kg/km)24,0CABLE WT. (kg/km)34,0Availability
On request
SECTION (mm²)4RESISTANCE (Ω/km)4,95CURRENT (air) (A)32INSUL. THK. (mm)0,8OUTER Ø (mm)4,2METAL WT. (kg/km)38,4CABLE WT. (kg/km)50,3Availability
On request
SECTION (mm²)6RESISTANCE (Ω/km)3,30CURRENT (air) (A)41INSUL. THK. (mm)0,8OUTER Ø (mm)4,7METAL WT. (kg/km)57,6CABLE WT. (kg/km)71,4Availability
On request
SECTION (mm²)10RESISTANCE (Ω/km)1,910CURRENT (air) (A)57INSUL. THK. (mm)1,0OUTER Ø (mm)6,1METAL WT. (kg/km)96,0CABLE WT. (kg/km)118,1Availability
On request
SECTION (mm²)16RESISTANCE (Ω/km)1,210CURRENT (air) (A)76INSUL. THK. (mm)1,0OUTER Ø (mm)7,2METAL WT. (kg/km)153,6CABLE WT. (kg/km)180,0Availability
On request
SECTION (mm²)25RESISTANCE (Ω/km)0,780CURRENT (air) (A)101INSUL. THK. (mm)1,2OUTER Ø (mm)8,4METAL WT. (kg/km)240,0CABLE WT. (kg/km)279,2Availability
On request
SECTION (mm²)35RESISTANCE (Ω/km)0,554CURRENT (air) (A)125INSUL. THK. (mm)1,2OUTER Ø (mm)9,5METAL WT. (kg/km)336,0CABLE WT. (kg/km)381,5Availability
On request
SECTION (mm²)50RESISTANCE (Ω/km)0,386CURRENT (air) (A)151INSUL. THK. (mm)1,4OUTER Ø (mm)11,3METAL WT. (kg/km)480,0CABLE WT. (kg/km)543,2Availability
On request
SECTION (mm²)70RESISTANCE (Ω/km)0,272CURRENT (air) (A)192INSUL. THK. (mm)1,4OUTER Ø (mm)12,6METAL WT. (kg/km)672,0CABLE WT. (kg/km)744,6Availability
On request
SECTION (mm²)95RESISTANCE (Ω/km)0,206CURRENT (air) (A)232INSUL. THK. (mm)1,6OUTER Ø (mm)14,7METAL WT. (kg/km)912,0CABLE WT. (kg/km)1008,9Availability
On request
SECTION (mm²)120RESISTANCE (Ω/km)0,161CURRENT (air) (A)269INSUL. THK. (mm)1,6OUTER Ø (mm)16,2METAL WT. (kg/km)1152,0CABLE WT. (kg/km)1259,6Availability
On request
SECTION (mm²)150RESISTANCE (Ω/km)0,129CURRENT (air) (A)300INSUL. THK. (mm)1,8OUTER Ø (mm)18,1METAL WT. (kg/km)1440,0CABLE WT. (kg/km)1574,9Availability
On request
SECTION (mm²)185RESISTANCE (Ω/km)0,106CURRENT (air) (A)341INSUL. THK. (mm)2,0OUTER Ø (mm)20,2METAL WT. (kg/km)1776,0CABLE WT. (kg/km)1942,2Availability
On request
SECTION (mm²)240RESISTANCE (Ω/km)0,0801CURRENT (air) (A)400INSUL. THK. (mm)2,2OUTER Ø (mm)22,9METAL WT. (kg/km)2304,0CABLE WT. (kg/km)2512,2Availability
On request

Prices for registered business customers · Registration takes 2 minutes

Sign inRegister

Construction

ConductorBakarno uže, klasa 5 / Cu rope, cl.5
InsulationPVC smeša / PVC compound
CPR classEca
Core IDEN 50525-1

Technical data

Voltage450 / 750 V
Test voltage2,5 kV
Bending8 × D (3 × D)
Max. cond.70 °C
Short-circuit160 °C
Laying temp.-5 °C

Application

For laying in pipes, on top of or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and distribution systems. Not suitable for direct laying under plaster.

Standards

IEC60227-3

EN 50525-2-31 · IEC 60227-3 · JUS N.C3.202 (P/F)