H07V-K
P/F · H07V-K · JUS N.C3.202
Low-voltage flexible PVC-insulated copper conductor (H07V-K · JUS P/F), class-5 stranded, 450/750 V.
Download datasheet (PDF)
Variants
| SECTION (mm²)0,75 | RESISTANCE (Ω/km)26,0 | CURRENT (air) (A)6 | INSUL. THK. (mm)0,6 | OUTER Ø (mm)2,3 | METAL WT. (kg/km)7,2 | CABLE WT. (kg/km)12,1 | Availability On request |
| SECTION (mm²)1 | RESISTANCE (Ω/km)19,5 | CURRENT (air) (A)10 | INSUL. THK. (mm)0,6 | OUTER Ø (mm)2,4 | METAL WT. (kg/km)9,6 | CABLE WT. (kg/km)14,8 | Availability On request |
| SECTION (mm²)1,5 | RESISTANCE (Ω/km)13,3 | CURRENT (air) (A)17,5 | INSUL. THK. (mm)0,7 | OUTER Ø (mm)3,0 | METAL WT. (kg/km)14,4 | CABLE WT. (kg/km)21,5 | Availability On request |
| SECTION (mm²)2,5 | RESISTANCE (Ω/km)7,98 | CURRENT (air) (A)24 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)3,6 | METAL WT. (kg/km)24,0 | CABLE WT. (kg/km)34,0 | Availability On request |
| SECTION (mm²)4 | RESISTANCE (Ω/km)4,95 | CURRENT (air) (A)32 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)4,2 | METAL WT. (kg/km)38,4 | CABLE WT. (kg/km)50,3 | Availability On request |
| SECTION (mm²)6 | RESISTANCE (Ω/km)3,30 | CURRENT (air) (A)41 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)4,7 | METAL WT. (kg/km)57,6 | CABLE WT. (kg/km)71,4 | Availability On request |
| SECTION (mm²)10 | RESISTANCE (Ω/km)1,910 | CURRENT (air) (A)57 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)6,1 | METAL WT. (kg/km)96,0 | CABLE WT. (kg/km)118,1 | Availability On request |
| SECTION (mm²)16 | RESISTANCE (Ω/km)1,210 | CURRENT (air) (A)76 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)7,2 | METAL WT. (kg/km)153,6 | CABLE WT. (kg/km)180,0 | Availability On request |
| SECTION (mm²)25 | RESISTANCE (Ω/km)0,780 | CURRENT (air) (A)101 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)8,4 | METAL WT. (kg/km)240,0 | CABLE WT. (kg/km)279,2 | Availability On request |
| SECTION (mm²)35 | RESISTANCE (Ω/km)0,554 | CURRENT (air) (A)125 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)9,5 | METAL WT. (kg/km)336,0 | CABLE WT. (kg/km)381,5 | Availability On request |
| SECTION (mm²)50 | RESISTANCE (Ω/km)0,386 | CURRENT (air) (A)151 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)11,3 | METAL WT. (kg/km)480,0 | CABLE WT. (kg/km)543,2 | Availability On request |
| SECTION (mm²)70 | RESISTANCE (Ω/km)0,272 | CURRENT (air) (A)192 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)12,6 | METAL WT. (kg/km)672,0 | CABLE WT. (kg/km)744,6 | Availability On request |
| SECTION (mm²)95 | RESISTANCE (Ω/km)0,206 | CURRENT (air) (A)232 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)14,7 | METAL WT. (kg/km)912,0 | CABLE WT. (kg/km)1008,9 | Availability On request |
| SECTION (mm²)120 | RESISTANCE (Ω/km)0,161 | CURRENT (air) (A)269 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)16,2 | METAL WT. (kg/km)1152,0 | CABLE WT. (kg/km)1259,6 | Availability On request |
| SECTION (mm²)150 | RESISTANCE (Ω/km)0,129 | CURRENT (air) (A)300 | INSUL. THK. (mm)1,8 | OUTER Ø (mm)18,1 | METAL WT. (kg/km)1440,0 | CABLE WT. (kg/km)1574,9 | Availability On request |
| SECTION (mm²)185 | RESISTANCE (Ω/km)0,106 | CURRENT (air) (A)341 | INSUL. THK. (mm)2,0 | OUTER Ø (mm)20,2 | METAL WT. (kg/km)1776,0 | CABLE WT. (kg/km)1942,2 | Availability On request |
| SECTION (mm²)240 | RESISTANCE (Ω/km)0,0801 | CURRENT (air) (A)400 | INSUL. THK. (mm)2,2 | OUTER Ø (mm)22,9 | METAL WT. (kg/km)2304,0 | CABLE WT. (kg/km)2512,2 | Availability On request |
Construction
ConductorBakarno uže, klasa 5 / Cu rope, cl.5
InsulationPVC smeša / PVC compound
CPR classEca
Core IDEN 50525-1
Technical data
Voltage450 / 750 V
Test voltage2,5 kV
Bending8 × D (3 × D)
Max. cond.70 °C
Short-circuit160 °C
Laying temp.-5 °C
Application
For laying in pipes, on top of or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and distribution systems. Not suitable for direct laying under plaster.
Standards
IEC60227-3
EN 50525-2-31 · IEC 60227-3 · JUS N.C3.202 (P/F)
Documents
H07V-K · PDF · 479 KBDownload datasheet (PDF)