H07V-R
P/M · H07V-R · JUS N.C3.200
Low-voltage PVC-insulated flexible copper conductor (H07V-R · JUS P/M), class-2 stranded, 450/750 V.
Download datasheet (PDF)
Variants
| SECTION (mm²)1,5 | RESISTANCE (Ω/km)12,1 | CURRENT (air) (A)17,5 | INSUL. THK. (mm)0,7 | OUTER Ø (mm)3,0 | METAL WT. (kg/km)14,4 | CABLE WT. (kg/km)23 | Availability On request |
| SECTION (mm²)2,5 | RESISTANCE (Ω/km)7,41 | CURRENT (air) (A)24 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)3,6 | METAL WT. (kg/km)24,0 | CABLE WT. (kg/km)35 | Availability On request |
| SECTION (mm²)4 | RESISTANCE (Ω/km)4,61 | CURRENT (air) (A)32 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)4,2 | METAL WT. (kg/km)38,4 | CABLE WT. (kg/km)51 | Availability On request |
| SECTION (mm²)6 | RESISTANCE (Ω/km)3,08 | CURRENT (air) (A)41 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)4,7 | METAL WT. (kg/km)57,6 | CABLE WT. (kg/km)71 | Availability On request |
| SECTION (mm²)10 | RESISTANCE (Ω/km)1,830 | CURRENT (air) (A)57 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)6,1 | METAL WT. (kg/km)96,0 | CABLE WT. (kg/km)120 | Availability On request |
| SECTION (mm²)16 | RESISTANCE (Ω/km)1,150 | CURRENT (air) (A)76 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)7,2 | METAL WT. (kg/km)153,6 | CABLE WT. (kg/km)180 | Availability On request |
| SECTION (mm²)25 | RESISTANCE (Ω/km)0,727 | CURRENT (air) (A)101 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)8,4 | METAL WT. (kg/km)240,0 | CABLE WT. (kg/km)280 | Availability On request |
| SECTION (mm²)35 | RESISTANCE (Ω/km)0,524 | CURRENT (air) (A)125 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)9,5 | METAL WT. (kg/km)336,0 | CABLE WT. (kg/km)380 | Availability On request |
| SECTION (mm²)50 | RESISTANCE (Ω/km)0,387 | CURRENT (air) (A)151 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)11,3 | METAL WT. (kg/km)480,0 | CABLE WT. (kg/km)490 | Availability On request |
| SECTION (mm²)70 | RESISTANCE (Ω/km)0,268 | CURRENT (air) (A)192 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)12,6 | METAL WT. (kg/km)672,0 | CABLE WT. (kg/km)710 | Availability On request |
| SECTION (mm²)95 | RESISTANCE (Ω/km)0,193 | CURRENT (air) (A)232 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)14,7 | METAL WT. (kg/km)912,0 | CABLE WT. (kg/km)980 | Availability On request |
| SECTION (mm²)120 | RESISTANCE (Ω/km)0,1530 | CURRENT (air) (A)269 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)16,2 | METAL WT. (kg/km)1152,0 | CABLE WT. (kg/km)1210 | Availability On request |
| SECTION (mm²)150 | RESISTANCE (Ω/km)0,1240 | CURRENT (air) (A)300 | INSUL. THK. (mm)1,8 | OUTER Ø (mm)18,1 | METAL WT. (kg/km)1440,0 | CABLE WT. (kg/km)1510 | Availability On request |
| SECTION (mm²)185 | RESISTANCE (Ω/km)0,0991 | CURRENT (air) (A)341 | INSUL. THK. (mm)2,0 | OUTER Ø (mm)20,2 | METAL WT. (kg/km)1776,0 | CABLE WT. (kg/km)1900 | Availability On request |
| SECTION (mm²)240 | RESISTANCE (Ω/km)0,0754 | CURRENT (air) (A)400 | INSUL. THK. (mm)2,2 | OUTER Ø (mm)22,9 | METAL WT. (kg/km)2304,0 | CABLE WT. (kg/km)2490 | Availability On request |
Construction
ConductorBakarno uže, klasa 2 / Cu rope, cl.2
InsulationPVC smeša / PVC compound
CPR classEca
Core IDEN 50525-1
Technical data
Voltage450 / 750 V
Test voltage2,5 kV
Bending6 × D
Max. cond.70 °C
Short-circuit160 °C
Sections1,5 – 240 mm²
Application
For laying in pipes, on top of or under plaster, in closed installation ducts and for internal wiring of machinery, switchgear and distribution systems. Not suitable for direct laying under plaster.
Standards
IEC60227
IEC60332-1
EN 50525-2-31 · IEC 60227 · IEC 60332-1 · JUS N.C3.200 (P/M)
Documents
H07V-R · PDF · 358 KBDownload datasheet (PDF)