H07V2-K
Low-voltage flexible PVC-insulated copper conductor rated 90 °C (H07V2-K), class-5 stranded, 450/750 V.
Download datasheet (PDF)
Variants
| SECTION (mm²)1,5 | RESISTANCE (Ω/km)13,3 | CURRENT (air) (A)24 | INSUL. THK. (mm)0,7 | OUTER Ø (mm)3,0 | METAL WT. (kg/km)14,4 | CABLE WT. (kg/km)22 | Availability On request |
| SECTION (mm²)2,5 | RESISTANCE (Ω/km)7,98 | CURRENT (air) (A)32 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)3,7 | METAL WT. (kg/km)24,0 | CABLE WT. (kg/km)35 | Availability On request |
| SECTION (mm²)4 | RESISTANCE (Ω/km)4,95 | CURRENT (air) (A)42 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)4,3 | METAL WT. (kg/km)38,4 | CABLE WT. (kg/km)52 | Availability On request |
| SECTION (mm²)6 | RESISTANCE (Ω/km)3,30 | CURRENT (air) (A)54 | INSUL. THK. (mm)0,8 | OUTER Ø (mm)5,0 | METAL WT. (kg/km)57,6 | CABLE WT. (kg/km)74 | Availability On request |
| SECTION (mm²)10 | RESISTANCE (Ω/km)1,910 | CURRENT (air) (A)73 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)6,5 | METAL WT. (kg/km)96,0 | CABLE WT. (kg/km)122 | Availability On request |
| SECTION (mm²)16 | RESISTANCE (Ω/km)1,210 | CURRENT (air) (A)98 | INSUL. THK. (mm)1,0 | OUTER Ø (mm)7,8 | METAL WT. (kg/km)153,6 | CABLE WT. (kg/km)186 | Availability On request |
| SECTION (mm²)25 | RESISTANCE (Ω/km)0,780 | CURRENT (air) (A)129 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)9,8 | METAL WT. (kg/km)240,0 | CABLE WT. (kg/km)290 | Availability On request |
| SECTION (mm²)35 | RESISTANCE (Ω/km)0,554 | CURRENT (air) (A)158 | INSUL. THK. (mm)1,2 | OUTER Ø (mm)10,9 | METAL WT. (kg/km)336,0 | CABLE WT. (kg/km)392 | Availability On request |
| SECTION (mm²)50 | RESISTANCE (Ω/km)0,386 | CURRENT (air) (A)198 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)12,8 | METAL WT. (kg/km)480,0 | CABLE WT. (kg/km)557 | Availability On request |
| SECTION (mm²)70 | RESISTANCE (Ω/km)0,272 | CURRENT (air) (A)245 | INSUL. THK. (mm)1,4 | OUTER Ø (mm)14,5 | METAL WT. (kg/km)672,0 | CABLE WT. (kg/km)760 | Availability On request |
| SECTION (mm²)95 | RESISTANCE (Ω/km)0,206 | CURRENT (air) (A)292 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)16,7 | METAL WT. (kg/km)912,0 | CABLE WT. (kg/km)1028 | Availability On request |
| SECTION (mm²)120 | RESISTANCE (Ω/km)0,161 | CURRENT (air) (A)344 | INSUL. THK. (mm)1,6 | OUTER Ø (mm)19,0 | METAL WT. (kg/km)1152,0 | CABLE WT. (kg/km)1286 | Availability On request |
| SECTION (mm²)150 | RESISTANCE (Ω/km)0,129 | CURRENT (air) (A)391 | INSUL. THK. (mm)1,8 | OUTER Ø (mm)20,7 | METAL WT. (kg/km)1440,0 | CABLE WT. (kg/km)1603 | Availability On request |
| SECTION (mm²)185 | RESISTANCE (Ω/km)0,106 | CURRENT (air) (A)448 | INSUL. THK. (mm)2,0 | OUTER Ø (mm)23,0 | METAL WT. (kg/km)1776,0 | CABLE WT. (kg/km)1978 | Availability On request |
| SECTION (mm²)240 | RESISTANCE (Ω/km)0,0801 | CURRENT (air) (A)528 | INSUL. THK. (mm)2,2 | OUTER Ø (mm)26,1 | METAL WT. (kg/km)2304,0 | CABLE WT. (kg/km)2557 | Availability On request |
Construction
ConductorBakarno uže, klasa 5 / Cu rope, cl.5
InsulationPVC smeša, tip TI3 / PVC, type TI3
Temp. rating90 °C (EN 50363-3)
Core IDEN 50525-1
Technical data
Voltage450 / 750 V
Test voltage2,5 kV
Bending6 × D
Max. cond.90 °C
Short-circuit160 °C
Class5 (EN 60228)
Application
For laying in installation tubes, on and under plaster in dry rooms and in closed ducts. For internal wiring of distribution and switching equipment, and lighting circuits up to 1000 V AC or 750 V DC to earth.
Standards
IEC60227
EN 50525-2-31 · IEC 60227