Skip to content

Prices for registered businessesRegister

CopperCoreCOPPERCORE

JE-H(St)H

Fire-resistant halogen-free signal cable (JE-H(St)H…Bd FE180/PH120) with silicone insulation and orange HFFR sheath.

Download datasheet (PDF)
Fire-resistant halogen-free signal cable (JE-H(St)H…Bd FE180/PH120) with silicone insulation and orange HFFR sheath.

Variants

PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×0,6OUTER Ø (mm)4,7CABLE WT. (kg/km)27Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×0,6OUTER Ø (mm)5,1CABLE WT. (kg/km)36Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×0,6OUTER Ø (mm)6,2CABLE WT. (kg/km)49Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×0,6OUTER Ø (mm)6,6CABLE WT. (kg/km)58Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×0,6OUTER Ø (mm)7,5CABLE WT. (kg/km)76Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×0,6OUTER Ø (mm)8,2CABLE WT. (kg/km)93Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×0,6OUTER Ø (mm)9,1CABLE WT. (kg/km)110Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×0,8OUTER Ø (mm)5,8CABLE WT. (kg/km)43Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×0,8OUTER Ø (mm)6,5CABLE WT. (kg/km)61Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×0,8OUTER Ø (mm)8,1CABLE WT. (kg/km)83Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×0,8OUTER Ø (mm)8,7CABLE WT. (kg/km)99Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×0,8OUTER Ø (mm)10,1CABLE WT. (kg/km)133Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×0,8OUTER Ø (mm)11,3CABLE WT. (kg/km)168Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×0,8OUTER Ø (mm)13,0CABLE WT. (kg/km)213Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×1,0OUTER Ø (mm)6,7CABLE WT. (kg/km)56Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×1,0OUTER Ø (mm)7,5CABLE WT. (kg/km)82Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×1,0OUTER Ø (mm)9,6CABLE WT. (kg/km)115Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×1,0OUTER Ø (mm)10,5CABLE WT. (kg/km)143Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×1,0OUTER Ø (mm)12,7CABLE WT. (kg/km)206Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×1,0OUTER Ø (mm)14,1CABLE WT. (kg/km)258Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×1,0OUTER Ø (mm)15,9CABLE WT. (kg/km)314Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×1,5OUTER Ø (mm)7,8CABLE WT. (kg/km)78Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×1,5OUTER Ø (mm)8,9CABLE WT. (kg/km)122Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×1,5OUTER Ø (mm)11,5CABLE WT. (kg/km)172Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×1,5OUTER Ø (mm)13,0CABLE WT. (kg/km)229Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×1,5OUTER Ø (mm)15,3CABLE WT. (kg/km)316Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×1,5OUTER Ø (mm)17,2CABLE WT. (kg/km)406Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×1,5OUTER Ø (mm)19,8CABLE WT. (kg/km)512Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×2,5OUTER Ø (mm)8,9CABLE WT. (kg/km)105Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×2,5OUTER Ø (mm)10,3CABLE WT. (kg/km)172Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×2,5OUTER Ø (mm)13,9CABLE WT. (kg/km)261Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×2,5OUTER Ø (mm)15,2CABLE WT. (kg/km)328Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×2,5OUTER Ø (mm)18,5CABLE WT. (kg/km)481Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×2,5OUTER Ø (mm)20,7CABLE WT. (kg/km)614Availability
On request
PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×2,5OUTER Ø (mm)23,9CABLE WT. (kg/km)778Availability
On request

Prices for registered business customers · Registration takes 2 minutes

Sign inRegister

Reference tables

Ø / SECTION (mm · mm²)0,6 mmLOOP RESIST. (Ω/km)130TEST VOLTAGE (V DC)500
Ø / SECTION (mm · mm²)0,8 mmLOOP RESIST. (Ω/km)73,2TEST VOLTAGE (V DC)500
Ø / SECTION (mm · mm²)1,0 mmLOOP RESIST. (Ω/km)44,6TEST VOLTAGE (V DC)1000
Ø / SECTION (mm · mm²)1,5 mm²LOOP RESIST. (Ω/km)24,6TEST VOLTAGE (V DC)1000
Ø / SECTION (mm · mm²)2,5 mm²LOOP RESIST. (Ω/km)15,1TEST VOLTAGE (V DC)1000

Construction

ConductorCu puna žica, klasa 1 / solid Cu, cl. 1
InsulationSilikonska, boje po VDE 0815 / silicone
Stranding2 parice: četvorka; više: slojevi
WrappingTraka od staklenih vlakana / glass fibre
ScreenAl-PES traka + kalajis. Cu drain žica
SheathHFFR, narandžasti RAL 2008 / orange

Technical data

Operating voltage225 V
Test voltage0,5 / 1 kV DC (1 min)
Capacitance120 nF/km
Operating temp.-30 … +70 °C
Bending radius10 × D
Circuit integrityFE180 / PH120

Application

For densely occupied premises, fire-alarm and security systems, signal transmission, instrumentation and industrial electronics — where circuit integrity in fire is required.

Standards

IEC60331-23

VDE 0815 · IEC 60331-23 · EN 50200 · EN 60332-1-2

Documents

JE-H(St)H · PDF · 4.0 MBDownload datasheet (PDF)