JE-H(St)H E30E90
Fire-resistant halogen-free signal / instrumentation cable JE-H(St)H Bd with ceramifiable insulation and orange HFFR sheath; E30/E90 circuit integrity.
Download datasheet (PDF)
Variants
| PAIRS × Ø (n×2×mm)1×2×0,8 | OUTER Ø (mm)5,4 | COPPER WT. (kg/km)14,3 | CABLE WT. (kg/km)38 | Availability On request |
| PAIRS × Ø (n×2×mm)2×2×0,8 | OUTER Ø (mm)6,2 | COPPER WT. (kg/km)23,8 | CABLE WT. (kg/km)54 | Availability On request |
| PAIRS × Ø (n×2×mm)3×2×0,8 | OUTER Ø (mm)7,9 | COPPER WT. (kg/km)33,4 | CABLE WT. (kg/km)80 | Availability On request |
| PAIRS × Ø (n×2×mm)4×2×0,8 | OUTER Ø (mm)9,5 | COPPER WT. (kg/km)42,9 | CABLE WT. (kg/km)103 | Availability On request |
| PAIRS × Ø (n×2×mm)5×2×0,8 | OUTER Ø (mm)9,8 | COPPER WT. (kg/km)52,4 | CABLE WT. (kg/km)119 | Availability On request |
| PAIRS × Ø (n×2×mm)6×2×0,8 | OUTER Ø (mm)11,9 | COPPER WT. (kg/km)62 | CABLE WT. (kg/km)144 | Availability On request |
| PAIRS × Ø (n×2×mm)8×2×0,8 | OUTER Ø (mm)12,3 | COPPER WT. (kg/km)81 | CABLE WT. (kg/km)178 | Availability On request |
| PAIRS × Ø (n×2×mm)10×2×0,8 | OUTER Ø (mm)12,8 | COPPER WT. (kg/km)100,1 | CABLE WT. (kg/km)208 | Availability On request |
Reference tables
| Ø / SECTION (mm · mm²)0,6 mm | LOOP RESIST. (Ω/km)130 | INSUL. RESIST. (MΩ/km)100 | CAPACITANCE (nF/km)100 | OPERATING V (V DC)300 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)0,8 mm | LOOP RESIST. (Ω/km)73,2 | INSUL. RESIST. (MΩ/km)100 | CAPACITANCE (nF/km)100 | OPERATING V (V DC)300 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)1,0 mm | LOOP RESIST. (Ω/km)44,6 | INSUL. RESIST. (MΩ/km)100 | CAPACITANCE (nF/km)100 | OPERATING V (V DC)300 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)1,5 mm² | LOOP RESIST. (Ω/km)24,6 | INSUL. RESIST. (MΩ/km)100 | CAPACITANCE (nF/km)100 | OPERATING V (V DC)300 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)2,5 mm² | LOOP RESIST. (Ω/km)15,1 | INSUL. RESIST. (MΩ/km)100 | CAPACITANCE (nF/km)100 | OPERATING V (V DC)300 | TEST VOLTAGE (V DC)1000 |
Construction
ConductorCu puna žica, klasa 1 / solid Cu, cl. 1 (EN 60228)
InsulationUmreženi keramizujući polimer / ceramifiable XLPE (VDE 0815)
StrandingParice; 4 parice → grupe; grupe u slojevima
WrappingPET traka + traka staklenih vlakana / glass yarn
ScreenKalajis. Cu drain žica + Al/PET traka
SheathHFFR, narandžasti RAL 2008 / orange
Technical data
Operating voltage300 V DC
Test voltage1 kV DC (1 min)
Capacitance100 nF/km
Operating temp.-40 … +70 °C
Bending radius10 × D
Circuit integrityFE180 · E30–E90 · PH120
Application
For fire-alarm and security systems, instrumentation and control, industrial electronics, VFD motor feeders and signal transmission — where circuit integrity in fire is required.
Standards
IEC60331-23
IEC60332-3-24
DIN VDE 0815 · IEC 60331-23 · EN 50200 · DIN 4102-12 (E30/E90) · IEC 60332-3-24
Documents
JE-H(St)H E30E90 · PDF · 368 KBDownload datasheet (PDF)