NAYCY
PP40-A · NAYCY
Power cable 0,6/1 kV with stranded aluminium conductor, PVC insulation and concentric copper wire screen (NAYCY · JUS PP40-A).
Download datasheet (PDF)
Variants
| SECTION (ph/sc) (mm²/mm²)1×25/16 | OUTER Ø (mm)16,0 | WEIGHT (kg/km)400 | DC RESISTANCE (Ω/km)1,20 | EARTH, FLAT (A)125 | EARTH, TREFOIL (A)105 | AIR, FLAT (A)87 | AIR, TREFOIL (A)75 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×35/16 | OUTER Ø (mm)17,0 | WEIGHT (kg/km)450 | DC RESISTANCE (Ω/km)0,868 | EARTH, FLAT (A)151 | EARTH, TREFOIL (A)127 | AIR, FLAT (A)131 | AIR, TREFOIL (A)113 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×50/25 | OUTER Ø (mm)19,5 | WEIGHT (kg/km)630 | DC RESISTANCE (Ω/km)0,641 | EARTH, FLAT (A)179 | EARTH, TREFOIL (A)151 | AIR, FLAT (A)160 | AIR, TREFOIL (A)138 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×70/35 | OUTER Ø (mm)20,5 | WEIGHT (kg/km)800 | DC RESISTANCE (Ω/km)0,443 | EARTH, FLAT (A)218 | EARTH, TREFOIL (A)186 | AIR, FLAT (A)202 | AIR, TREFOIL (A)174 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×95/50 | OUTER Ø (mm)24,0 | WEIGHT (kg/km)1050 | DC RESISTANCE (Ω/km)0,320 | EARTH, FLAT (A)261 | EARTH, TREFOIL (A)223 | AIR, FLAT (A)249 | AIR, TREFOIL (A)210 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×120/70 | OUTER Ø (mm)26,0 | WEIGHT (kg/km)1350 | DC RESISTANCE (Ω/km)0,253 | EARTH, FLAT (A)297 | EARTH, TREFOIL (A)254 | AIR, FLAT (A)291 | AIR, TREFOIL (A)244 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×150/70 | OUTER Ø (mm)27,5 | WEIGHT (kg/km)1500 | DC RESISTANCE (Ω/km)0,206 | EARTH, FLAT (A)332 | EARTH, TREFOIL (A)285 | AIR, FLAT (A)333 | AIR, TREFOIL (A)281 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×185/95 | OUTER Ø (mm)30,0 | WEIGHT (kg/km)1850 | DC RESISTANCE (Ω/km)0,164 | EARTH, FLAT (A)376 | EARTH, TREFOIL (A)323 | AIR, FLAT (A)384 | AIR, TREFOIL (A)320 | Availability On request |
| SECTION (ph/sc) (mm²/mm²)1×240/120 | OUTER Ø (mm)33,5 | WEIGHT (kg/km)2350 | DC RESISTANCE (Ω/km)0,125 | EARTH, FLAT (A)437 | EARTH, TREFOIL (A)378 | AIR, FLAT (A)460 | AIR, TREFOIL (A)378 | Availability On request |
Reference tables
| SECTION (ph/sc) (mm²/mm²)3×25/16 | OUTER Ø (mm)25,0 | WEIGHT (kg/km)950 | DC RESISTANCE (Ω/km)1,20 | CURRENT EARTH (A)99 | CURRENT AIR (A)83 |
| SECTION (ph/sc) (mm²/mm²)3×35/16 | OUTER Ø (mm)27,5 | WEIGHT (kg/km)1100 | DC RESISTANCE (Ω/km)0,868 | CURRENT EARTH (A)118 | CURRENT AIR (A)102 |
| SECTION (ph/sc) (mm²/mm²)3×50/25 | OUTER Ø (mm)32,0 | WEIGHT (kg/km)1500 | DC RESISTANCE (Ω/km)0,641 | CURRENT EARTH (A)142 | CURRENT AIR (A)124 |
| SECTION (ph/sc) (mm²/mm²)3×70/35 | OUTER Ø (mm)36,0 | WEIGHT (kg/km)2000 | DC RESISTANCE (Ω/km)0,443 | CURRENT EARTH (A)176 | CURRENT AIR (A)158 |
| SECTION (ph/sc) (mm²/mm²)3×95/50 | OUTER Ø (mm)41,5 | WEIGHT (kg/km)2650 | DC RESISTANCE (Ω/km)0,320 | CURRENT EARTH (A)211 | CURRENT AIR (A)190 |
| SECTION (ph/sc) (mm²/mm²)3×120/70 | OUTER Ø (mm)45,0 | WEIGHT (kg/km)3250 | DC RESISTANCE (Ω/km)0,253 | CURRENT EARTH (A)242 | CURRENT AIR (A)221 |
| SECTION (ph/sc) (mm²/mm²)3×150/70 | OUTER Ø (mm)50,0 | WEIGHT (kg/km)3850 | DC RESISTANCE (Ω/km)0,206 | CURRENT EARTH (A)270 | CURRENT AIR (A)252 |
| SECTION (ph/sc) (mm²/mm²)3×185/95 | OUTER Ø (mm)55,0 | WEIGHT (kg/km)4900 | DC RESISTANCE (Ω/km)0,164 | CURRENT EARTH (A)308 | CURRENT AIR (A)289 |
| SECTION (ph/sc) (mm²/mm²)3×240/120 | OUTER Ø (mm)61,5 | WEIGHT (kg/km)6100 | DC RESISTANCE (Ω/km)0,125 | CURRENT EARTH (A)363 | CURRENT AIR (A)339 |
| SECTION (ph/sc) (mm²/mm²)3×300/150 | OUTER Ø (mm)68,0 | WEIGHT (kg/km)7450 | DC RESISTANCE (Ω/km)0,100 | CURRENT EARTH (A)412 | CURRENT AIR (A)377 |
| SECTION (ph/sc) (mm²/mm²)3×400/185 | OUTER Ø (mm)77,5 | WEIGHT (kg/km)9600 | DC RESISTANCE (Ω/km)0,0778 | CURRENT EARTH (A)475 | CURRENT AIR (A)444 |
Construction
ConductorAl uže / Stranded Al (R)
InsulationPVC smeša / PVC compound
BeddingPVC (1-žilni: unutrašnji plašt)
ConcentricCu žice + Cu traka / Cu wires + tape
BinderPoliester traka / Polyester tape
SheathPVC / PVC outer jacket
Technical data
Voltage0,6 / 1 kV
CodeYAVCV-R (NAYCY)
Max. operating70 °C
Short-circuit160 °C (maks. 5 s)
SC > 300 mm²140 °C
Bending15 × D
Application
For indoor installations, ducts, outdoor and underground use — for power stations, industry and local supply systems where increased protection is needed. The screen prevents power leakage if the cable is damaged.
Standards
IEC60502-1
IEC 60502-1 · VDE 0276-603 · JUS PP40-A
Documents
NAYCY · PDF · 404 KBDownload datasheet (PDF)