J-Y(St)Y
Installation signal cable for fire-alarm and telephone systems (J-Y(St)Y…Lg), solid Cu conductors, static screen, red PVC sheath.
Download datasheet (PDF)
Variants
| PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×0,6 | OUTER Ø (mm)4,40 | CABLE WT. (kg/km)24 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×0,6 | OUTER Ø (mm)5,10 | CABLE WT. (kg/km)35 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×0,6 | OUTER Ø (mm)6,10 | CABLE WT. (kg/km)47 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×0,6 | OUTER Ø (mm)6,50 | CABLE WT. (kg/km)56 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))5×2×0,6 | OUTER Ø (mm)7,00 | CABLE WT. (kg/km)65 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×0,6 | OUTER Ø (mm)7,50 | CABLE WT. (kg/km)74 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×0,6 | OUTER Ø (mm)9,00 | CABLE WT. (kg/km)111 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))12×2×0,6 | OUTER Ø (mm)9,40 | CABLE WT. (kg/km)127 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))14×2×0,6 | OUTER Ø (mm)9,90 | CABLE WT. (kg/km)143 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))16×2×0,6 | OUTER Ø (mm)10,40 | CABLE WT. (kg/km)159 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))20×2×0,6 | OUTER Ø (mm)11,30 | CABLE WT. (kg/km)191 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×0,8 | OUTER Ø (mm)5,60 | CABLE WT. (kg/km)38 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×0,8 | OUTER Ø (mm)6,70 | CABLE WT. (kg/km)57 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))3×2×0,8 | OUTER Ø (mm)8,20 | CABLE WT. (kg/km)79 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×0,8 | OUTER Ø (mm)9,00 | CABLE WT. (kg/km)97 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))6×2×0,8 | OUTER Ø (mm)10,60 | CABLE WT. (kg/km)132 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))8×2×0,8 | OUTER Ø (mm)11,20 | CABLE WT. (kg/km)164 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))10×2×0,8 | OUTER Ø (mm)13,20 | CABLE WT. (kg/km)213 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))12×2×0,8 | OUTER Ø (mm)13,80 | CABLE WT. (kg/km)245 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))14×2×0,8 | OUTER Ø (mm)14,70 | CABLE WT. (kg/km)279 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))16×2×0,8 | OUTER Ø (mm)15,50 | CABLE WT. (kg/km)311 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))20×2×0,8 | OUTER Ø (mm)17,00 | CABLE WT. (kg/km)377 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×1,0 | OUTER Ø (mm)6,20 | CABLE WT. (kg/km)56 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×1,0 | OUTER Ø (mm)8,10 | CABLE WT. (kg/km)86 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×1,0 | OUTER Ø (mm)10,60 | CABLE WT. (kg/km)165 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×1,5 | OUTER Ø (mm)6,80 | CABLE WT. (kg/km)71 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×1,5 | OUTER Ø (mm)9,60 | CABLE WT. (kg/km)126 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×1,5 | OUTER Ø (mm)11,30 | CABLE WT. (kg/km)199 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))1×2×2,5 | OUTER Ø (mm)7,80 | CABLE WT. (kg/km)98 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))2×2×2,5 | OUTER Ø (mm)10,60 | CABLE WT. (kg/km)168 | Availability On request |
| PAIRS × Ø/SECT. (n×2×(mm·mm²))4×2×2,5 | OUTER Ø (mm)14,10 | CABLE WT. (kg/km)314 | Availability On request |
Reference tables
| Ø / SECTION (mm · mm²)0,6 mm | LOOP RESIST. (Ω/km)130 | TEST VOLTAGE (V DC)800 |
| Ø / SECTION (mm · mm²)0,8 mm | LOOP RESIST. (Ω/km)73,2 | TEST VOLTAGE (V DC)800 |
| Ø / SECTION (mm · mm²)1,0 mm | LOOP RESIST. (Ω/km)44,6 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)1,5 mm² | LOOP RESIST. (Ω/km)24,6 | TEST VOLTAGE (V DC)1000 |
| Ø / SECTION (mm · mm²)2,5 mm² | LOOP RESIST. (Ω/km)15,1 | TEST VOLTAGE (V DC)1000 |
Construction
ConductorCu puna žica, klasa 1 / solid Cu, cl. 1
InsulationPVC u bojama (VDE 0815)
StrandingParice u slojevima; 2-par.: četvorka
WrappingPES traka / PES tape
ScreenAl-PES traka + kalajis. Cu drain žica
SheathPVC, crveni RAL 3000 / red PVC
Technical data
Operating voltage300 V
Test voltage0,8 / 1 kV DC (1 min)
Capacitance100 nF/km
Operating temp.-30 … +70 °C
Bending radius10 × D
Flame testEN 60332-1-2
Application
For areas with electromagnetic interference — instrumentation and control, industrial electronics, computers, indoor communication and sound systems, fire-alarm and security systems.
Standards
DIN VDE 0815 · EN 60332-1-2
Documents
J-Y(St)Y · PDF · 600 KBDownload datasheet (PDF)