Skip to content

Prices for registered businessesRegister

CopperCoreCOPPERCORE

LiHCH FE180PH90

Fire-resistant halogen-free (HFFR) screened signal/control cable with ceramic-forming XLPE insulation, tinned Cu braid screen and orange RAL 2003 sheath; VDE 0812.

Download datasheet (PDF)
Fire-resistant halogen-free (HFFR) screened signal/control cable with ceramic-forming XLPE insulation, tinned Cu braid screen and orange RAL 2003 sheath; VDE 0812.

Variants

SECTION (mm²)0,22RESISTANCE (Ω/km)79INSUL. RES. (MΩ·km)200CURRENT (A)2,5Availability
On request
SECTION (mm²)0,34RESISTANCE (Ω/km)56INSUL. RES. (MΩ·km)200CURRENT (A)4,5Availability
On request
SECTION (mm²)0,5RESISTANCE (Ω/km)39INSUL. RES. (MΩ·km)20CURRENT (A)6Availability
On request
SECTION (mm²)0,75RESISTANCE (Ω/km)26INSUL. RES. (MΩ·km)20CURRENT (A)13Availability
On request
SECTION (mm²)1RESISTANCE (Ω/km)19,5INSUL. RES. (MΩ·km)20CURRENT (A)16Availability
On request
SECTION (mm²)1,5RESISTANCE (Ω/km)13,3INSUL. RES. (MΩ·km)20CURRENT (A)20Availability
On request
SECTION (mm²)2,5RESISTANCE (Ω/km)7,98INSUL. RES. (MΩ·km)20CURRENT (A)25Availability
On request

Prices for registered business customers · Registration takes 2 minutes

Sign inRegister

Construction

ConductorCu uže kl. 5, EN 60228 / VDE 0295
InsulationKeramizirajuća, DIN 47100 boje
StrandingSlojevi opt. hoda / optimum pitch
WrappingPES + staklena traka / glass-fibre
ScreenKalajisana Cu pletenica / tinned Cu braid
SheathHFFR, RAL 2003 narandžasta / orange

Technical data

Rated voltage Uo/U300/500 V (250 V ≤0,34 mm²)
Test voltage2 kV (1,2 kV ≤0,34 mm²)
Capacitance120 nF/km
Operating temp.-40 … +70 °C
Bending radius7,5 × D
Fire integrityFE180 · PH120 · E30-E60

Application

For EMI environments and densely occupied areas: instrumentation and control, industrial electronics, computers, communication and sound systems, protection of people and equipment.

Standards

IEC60331-23 (FE180)
IEC60332-3-24
IEC61034-2
IEC60754-1/-2

VDE 0812 · IEC 60331-23 (FE180) · EN 50200 (PH120) · DIN 4102-12 (E30–E60) · IEC 60332-3-24 · IEC 61034-2 · IEC 60754-1/-2

Documents

LiHCH FE180PH90 · PDF · 341 KBDownload datasheet (PDF)