N2XSEYFGbY
XHP 85 · N2XSEYFGbY · SRPS N.C5.230
Medium-voltage three-core armoured cable 12/20 kV with copper conductors, XLPE insulation, Cu wire screen and flat steel wire armour (N2XSEYFGbY · JUS XHP 85).
Download datasheet (PDF)
Variants
| SECTION (ph/scr) (mm²)3×35/16 | OUTER Ø (mm)61,0 | WEIGHT (kg/km)5750 | DC RESISTANCE (Ω/km)0,524 | CAPACITANCE (µF/km)0,41 | INDUCTANCE (mH/km)0,14 | GROUND (20 °C) (A)175 | AIR (30 °C) (A)172 | Availability On request |
| SECTION (ph/scr) (mm²)3×50/16 | OUTER Ø (mm)64,0 | WEIGHT (kg/km)6550 | DC RESISTANCE (Ω/km)0,387 | CAPACITANCE (µF/km)0,39 | INDUCTANCE (mH/km)0,15 | GROUND (20 °C) (A)205 | AIR (30 °C) (A)205 | Availability On request |
| SECTION (ph/scr) (mm²)3×70/16 | OUTER Ø (mm)68,0 | WEIGHT (kg/km)7650 | DC RESISTANCE (Ω/km)0,268 | CAPACITANCE (µF/km)0,37 | INDUCTANCE (mH/km)0,17 | GROUND (20 °C) (A)252 | AIR (30 °C) (A)253 | Availability On request |
| SECTION (ph/scr) (mm²)3×95/16 | OUTER Ø (mm)72,0 | WEIGHT (kg/km)9000 | DC RESISTANCE (Ω/km)0,193 | CAPACITANCE (µF/km)0,35 | INDUCTANCE (mH/km)0,19 | GROUND (20 °C) (A)305 | AIR (30 °C) (A)307 | Availability On request |
| SECTION (ph/scr) (mm²)3×120/16 | OUTER Ø (mm)76,0 | WEIGHT (kg/km)10100 | DC RESISTANCE (Ω/km)0,153 | CAPACITANCE (µF/km)0,34 | INDUCTANCE (mH/km)0,21 | GROUND (20 °C) (A)350 | AIR (30 °C) (A)352 | Availability On request |
| SECTION (ph/scr) (mm²)3×150/25 | OUTER Ø (mm)79,0 | WEIGHT (kg/km)11550 | DC RESISTANCE (Ω/km)0,124 | CAPACITANCE (µF/km)0,32 | INDUCTANCE (mH/km)0,22 | GROUND (20 °C) (A)392 | AIR (30 °C) (A)397 | Availability On request |
| SECTION (ph/scr) (mm²)3×185/25 | OUTER Ø (mm)84,0 | WEIGHT (kg/km)13250 | DC RESISTANCE (Ω/km)0,0991 | CAPACITANCE (µF/km)0,31 | INDUCTANCE (mH/km)0,24 | GROUND (20 °C) (A)445 | AIR (30 °C) (A)453 | Availability On request |
| SECTION (ph/scr) (mm²)3×240/25 | OUTER Ø (mm)90,0 | WEIGHT (kg/km)15450 | DC RESISTANCE (Ω/km)0,0754 | CAPACITANCE (µF/km)0,3 | INDUCTANCE (mH/km)0,27 | GROUND (20 °C) (A)520 | AIR (30 °C) (A)529 | Availability On request |
| SECTION (ph/scr) (mm²)3×300/25 | OUTER Ø (mm)96,0 | WEIGHT (kg/km)18000 | DC RESISTANCE (Ω/km)0,0601 | CAPACITANCE (µF/km)0,29 | INDUCTANCE (mH/km)0,29 | GROUND (20 °C) (A)580 | AIR (30 °C) (A)626 | Availability On request |
| SECTION (ph/scr) (mm²)3×400/35 | OUTER Ø (mm)103,0 | WEIGHT (kg/km)21650 | DC RESISTANCE (Ω/km)0,0470 | CAPACITANCE (µF/km)0,28 | INDUCTANCE (mH/km)0,33 | GROUND (20 °C) (A)620 | AIR (30 °C) (A)720 | Availability On request |
Construction
ConductorCu, okrugli užetani (RM), kl.2
InsulationXLPE + poluprovodni slojevi
ScreenCu žice + Cu traka
ArmourPljosnate pocink. čelične žice + traka
SheathPVC (razdvojni + spoljašnji)
Technical data
Rated voltage12/20 kV
Max. voltage24 kV
Max. operating90 °C
Short-circuit250 °C (maks. 5 s)
Bending15 × D
CodeYXC8VZ3V-R (TSE)
Application
For heavy mechanical duty: underground, in cable ducts, power distribution plants, city networks and industrial buildings.
Standards
SRPSN.C5.230 (XHP 85)
TS IEC 60502-2 · VDE 0276 · SRPS N.C5.230 (XHP 85)
Documents
N2XSEYFGbY · PDF · 387 KBDownload datasheet (PDF)