Skip to content

Prices for registered businessesRegister

CopperCoreCOPPERCORE

N2XSEYFGbY

XHP 85 · N2XSEYFGbY · SRPS N.C5.230

Medium-voltage three-core armoured cable 12/20 kV with copper conductors, XLPE insulation, Cu wire screen and flat steel wire armour (N2XSEYFGbY · JUS XHP 85).

Download datasheet (PDF)
Medium-voltage three-core armoured cable 12/20 kV with copper conductors, XLPE insulation, Cu wire screen and flat steel wire armour (N2XSEYFGbY · JUS XHP 85).

Variants

SECTION (ph/scr) (mm²)3×35/16OUTER Ø (mm)61,0WEIGHT (kg/km)5750DC RESISTANCE (Ω/km)0,524CAPACITANCE (µF/km)0,41INDUCTANCE (mH/km)0,14GROUND (20 °C) (A)175AIR (30 °C) (A)172Availability
On request
SECTION (ph/scr) (mm²)3×50/16OUTER Ø (mm)64,0WEIGHT (kg/km)6550DC RESISTANCE (Ω/km)0,387CAPACITANCE (µF/km)0,39INDUCTANCE (mH/km)0,15GROUND (20 °C) (A)205AIR (30 °C) (A)205Availability
On request
SECTION (ph/scr) (mm²)3×70/16OUTER Ø (mm)68,0WEIGHT (kg/km)7650DC RESISTANCE (Ω/km)0,268CAPACITANCE (µF/km)0,37INDUCTANCE (mH/km)0,17GROUND (20 °C) (A)252AIR (30 °C) (A)253Availability
On request
SECTION (ph/scr) (mm²)3×95/16OUTER Ø (mm)72,0WEIGHT (kg/km)9000DC RESISTANCE (Ω/km)0,193CAPACITANCE (µF/km)0,35INDUCTANCE (mH/km)0,19GROUND (20 °C) (A)305AIR (30 °C) (A)307Availability
On request
SECTION (ph/scr) (mm²)3×120/16OUTER Ø (mm)76,0WEIGHT (kg/km)10100DC RESISTANCE (Ω/km)0,153CAPACITANCE (µF/km)0,34INDUCTANCE (mH/km)0,21GROUND (20 °C) (A)350AIR (30 °C) (A)352Availability
On request
SECTION (ph/scr) (mm²)3×150/25OUTER Ø (mm)79,0WEIGHT (kg/km)11550DC RESISTANCE (Ω/km)0,124CAPACITANCE (µF/km)0,32INDUCTANCE (mH/km)0,22GROUND (20 °C) (A)392AIR (30 °C) (A)397Availability
On request
SECTION (ph/scr) (mm²)3×185/25OUTER Ø (mm)84,0WEIGHT (kg/km)13250DC RESISTANCE (Ω/km)0,0991CAPACITANCE (µF/km)0,31INDUCTANCE (mH/km)0,24GROUND (20 °C) (A)445AIR (30 °C) (A)453Availability
On request
SECTION (ph/scr) (mm²)3×240/25OUTER Ø (mm)90,0WEIGHT (kg/km)15450DC RESISTANCE (Ω/km)0,0754CAPACITANCE (µF/km)0,3INDUCTANCE (mH/km)0,27GROUND (20 °C) (A)520AIR (30 °C) (A)529Availability
On request
SECTION (ph/scr) (mm²)3×300/25OUTER Ø (mm)96,0WEIGHT (kg/km)18000DC RESISTANCE (Ω/km)0,0601CAPACITANCE (µF/km)0,29INDUCTANCE (mH/km)0,29GROUND (20 °C) (A)580AIR (30 °C) (A)626Availability
On request
SECTION (ph/scr) (mm²)3×400/35OUTER Ø (mm)103,0WEIGHT (kg/km)21650DC RESISTANCE (Ω/km)0,0470CAPACITANCE (µF/km)0,28INDUCTANCE (mH/km)0,33GROUND (20 °C) (A)620AIR (30 °C) (A)720Availability
On request

Prices for registered business customers · Registration takes 2 minutes

Sign inRegister

Construction

ConductorCu, okrugli užetani (RM), kl.2
InsulationXLPE + poluprovodni slojevi
ScreenCu žice + Cu traka
ArmourPljosnate pocink. čelične žice + traka
SheathPVC (razdvojni + spoljašnji)

Technical data

Rated voltage12/20 kV
Max. voltage24 kV
Max. operating90 °C
Short-circuit250 °C (maks. 5 s)
Bending15 × D
CodeYXC8VZ3V-R (TSE)

Application

For heavy mechanical duty: underground, in cable ducts, power distribution plants, city networks and industrial buildings.

Standards

SRPSN.C5.230 (XHP 85)

TS IEC 60502-2 · VDE 0276 · SRPS N.C5.230 (XHP 85)